Review Details: COMMERCIAL TI
Permit Number - T08CM03809
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/04/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
12/04/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006 |
12/04/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
12/04/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/04/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | CANNOT ACCESS TOILET THROUGH STORAGE ROOM. RELOCATE TOILET ROOM |
12/04/2008 | DROBEY1 | WWM | REVIEW | Needs Review | |
12/04/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006. 2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006. 3. If the reduced pressure backflow reventer is locate over 5'-0" above the finished floor, relocate the reduced pressure backflow preventer to conform to the access and clearance requirements of Section 603.3.4, UPC 2006 |
12/04/2008 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
12/04/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
12/04/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | RELOCATE TOILET, NEW DESIGN NEEDS TO BE REVIEWED |
12/04/2008 | RBROWN1 | ADA | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/04/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |