Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03809
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03809
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/04/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
12/04/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006
12/04/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/04/2008 ROBERT SHERRY WATER REVIEW Approved
12/04/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied CANNOT ACCESS TOILET THROUGH STORAGE ROOM. RELOCATE TOILET ROOM
12/04/2008 DROBEY1 WWM REVIEW Needs Review
12/04/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006.
2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
3. If the reduced pressure backflow reventer is locate over 5'-0" above the finished floor, relocate the reduced pressure backflow preventer to conform to the access and clearance requirements of Section 603.3.4, UPC 2006
12/04/2008 LOREN MAKUS ENGINEERING REVIEW Approved
12/04/2008 DAVE MANN FIRE REVIEW Approved
12/04/2008 RONALD BROWN ZONING HC SITE REVIEW Denied RELOCATE TOILET, NEW DESIGN NEEDS TO BE REVIEWED
12/04/2008 RBROWN1 ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2008 DELMA ROBEY OUT TO CUSTOMER Completed