Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03806
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/21/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; revisions still result in velocities greater than 8 fps with Type L copper. Limit the water velocity to less than 8 fps for the copper piping (pipe sizing chart, 1-1/4", 1-1/2", and 2"). Reference: Section A 6.1, UPC 2003; IAPMO IS 3-2003, Section 610.0. |
01/21/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/22/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S1.0; SECTION 01: PROVIDE A CONNECTION ON THE DRAWING BETWEEN THE NEW CONDENSER WOOD PLATFORM AND THE EXISTING ROOF STRUCTURE. |
02/09/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/12/2009 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
02/12/2009 | SUE REEVES | REJECT SHELF | Completed |