Permit Number: T08CM03806
Parcel: 137055350

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03806
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved; revisions still result in velocities greater than 8 fps with Type L copper. Limit the water velocity to less than 8 fps for the copper piping (pipe sizing chart, 1-1/4", 1-1/2", and 2"). Reference: Section A 6.1, UPC 2003; IAPMO IS 3-2003, Section 610.0.
01/21/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/22/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.0; SECTION 01: PROVIDE A CONNECTION ON THE DRAWING BETWEEN THE NEW CONDENSER WOOD PLATFORM AND THE EXISTING ROOF STRUCTURE.
02/09/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/12/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
02/12/2009 SUE REEVES REJECT SHELF Completed