Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/22/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
12/04/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
12/10/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/16/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project ; T08CM03806 TI Urgent Care 5369 S Calle Santa Cruz The electrical plan has been denied for the following items: The Interior Lighting Compliance Calculation appears to be for another project, project for Nextcare at Old Spanish Trail, the square footage is different. Ray T Majuta Electrical Plan Ck DSD City of Tucson 12-16-08 520-837-4988 |
12/26/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
12/30/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Limit the water velocity to less than 8 fps for the copper piping (pipe sizing chart, 1-1/4", 1-1/2", and 2"). Reference: Section A 6.1, UPC 2003; IAPMO IS 3-2003, Section 610.0. 2. Clarify the intent for the solenoid shut off valves for the lavatory in room 114. Reference: Section 103.2.3, UPC 2006. |
12/30/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/31/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. If the structural sketch that shows how the roof framing is to be modified for the installation of new mechanical units is to be use for this project, the sketch shall be made part of the drawing set, not an attachment. 2. Show how the new fan coil is being connected to the building structure. Reference: Section 302.1, IMC 2006. 3. Clarify the size, route, and termination of the auxiliary or secondary drain for fan coil unit and show that it is independent from the primary condensate drain for the fan coil. Reference: Section 307.2.3 IMC 2006 |