Permit Number - T08CM03801
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the medical gas storage room meets the requirements of Section 502.9.1, IMC 2006, and Section 3006, IFC 2006. 2. If the building energy compliance is not in accordance with ASHRAE 90.1, the duct insulation shall be determined by Section 503.2.7, IECC 2006, as amended by the City of Tucson. Reference: Section 501.2, IECC 2006, as amended by the City of Tucson. 3. Provide energy code compliance calculations. Reference: Section 101.4, International Energy Conservation Code 2006. |
| 01/02/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the intended use for the "utility wall plate". Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Specify the type of backflow prevention device required for each water connection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson. 2. Provide a cut sheet for the "vacuum pipe backflow preventor" (keynote 2/P-1.2). Reference: Section 103.2.3, UPC 2006. 3. Provide detail F/P-2.1 or coordinate the detail callouts if the detail is actually E/P-2.1. Reference: Section 103.2.3, UPC 2006. 4. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 5. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported (no detail provided by the architect). Reference: Sections 310.0 and 314.5, UPC 2006. 6. Provide sizing information for the roof scuppers and indicate the point of termination for the storm water discharge. (Note that the roof plan has not been sealed.) Reference: Section 1101.11, UPC 2006. 7. Provide a site utility plan that shows the property lines, the existing buildings, the water and fire service piping, and the building sewer, including the point of connection to the public sewer. Reference: Section 103.2.3, UPC 2006. 8. Provide the material specifications for the existing building sewer shown running under the proposed building. Reference: Section 103.2.3, UPC 2006. |
| 01/02/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Provide a site plan that shows the location of the water meter and backflow prevention assembly. Indicate the buildings that are served by the meter and the total connected demand. Reference: Section 103.2.3, UPC 2006 |
| 01/06/2009 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/08/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/09/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 8259 S Houghton Rd New Building Medical T08CM03801 The Electrical Plans have been denied for the following: 1.The building has an energized 800 amp service.which already has a grounding electrode system, in adding the one you show on sheet E-4, has consideration been take as to how the new 200 amp disconnects should be grounded as per the NEC 250. Show the existing and how the new grounding is to tie into the old. 2.Sheet E-4 on the one line diagram, the feeders shown from the new CT Can to the two 200 amp disconnects should show 4 #3/0,1#6 rather than 3 #3/0, 1#6. 3. Sheet E-3 lighting plan shows circuit B-20 feeding lights, the panel shows a spare. 4. Sheet E-3 cannot locate B-24, however a load is shown in panel. 5. Circuits B-34,36,and 38 are not shown on plan. 6. Sheet E-4, the circuits for B-25 and 27 are used twice. 7. Circuit numbers for water heater need to be written on sheet E-4. Ray T Majuta Elect Plan Ck DSD City of Tucson 520-837-4988 1/11/09 |
| 12/17/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING. 2. ALL DEFERRED SUBMITTALS MUST BE APPROVED IN WRITING BY THE BUILDING OFFICIAL, JESSIE SANDERS. 3. SHEET C-1: SUBMIT APPROVED SITE PLAN. SUBMITTED SITE PLAN DOES NOT MATCH BUILDING FOOTPRINT AS INDICATED ON SHEET A-1. ACCESSIBLE ROUTE INDICATED ON PLAN DOES NOT MATCH EXISTING CONDITIONS. 4. SHEET S-1: DID NOT LOCATE SECTION CUT 03/S5.0. VERIFY. |
| 12/18/2008 | DAVE MANN | FIRE | REVIEW | Denied | Please refer to 2006 IFC, Chapter 40 for general requirements for storage of oxidizing gases (nitrous and oxygen). Also, Section 3006.2.2 provides specific requirements for medical gases within buildings. Please provide on plans documentation that these requirements have been satisfied. |
| 12/18/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |