Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03793
Parcel: 105123390

Address:
4133 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03793
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2009 DAVE MANN FIRE REVIEW Denied It appears there are no fire hydrants anywhere close to the new building. The Fire Department requires either a fire hydrant within 300' of all parts of the building, or installation of fire sprinklers. Please indicate on drawings how fire protection requirements will be satisfied.
01/27/2009 GERRY KOZIOL WWM REVIEW Approved
01/29/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/02/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the route, slope, and connection point of the new building sewer to the existing private sewer collection system. Reference: Section 103.2.3, UPC 2006.
2. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006.
3. Show the materials for the new water service and water distribution piping and for the new building sewer and drain piping. Reference: Section 103.2.3, UPC 2006.
4. Provide cleanouts sized per Section 707.11, UPC 2006.
02/13/2009 ROBERT SHERRY WATER REVIEW Approved
02/17/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T08CM03793
4133 N STONE
ADDITION GARAGE AND CRAFT ROOM

The electrical plans have been denied for the following:
1. Per section 225-30 and 31 of the 2005 NEC, a main disconnect is required at the seperate structure. The panel would be allowed to have only six circuit breakers, the panel shown has more than six, therefore it requirs a main.
2.Section 250-32 of the NEC requires this structure to have it's own grounding system, include one in drawing and size.
3.Provide information on outside fixtures, cut sheet showing cut off, lamp type and lumen output. This is in order to verify compliance with City/County Outdoor Lighting ord # 10135.
4.Show location of existing 400 amp service, also provide load on this service and add new load to verify total.




Ray T Majuta
DSD City of Tucson
Electrical Plan Ck
2/18/09
520-873-4899

Final Status

Task End Date Reviewer's Name Type of Review Description
02/20/2009 CPIERCE1 OUT TO CUSTOMER Completed
02/20/2009 SUE REEVES REJECT SHELF Completed