Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T08CM03793
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/27/2009 | DAVE MANN | FIRE | REVIEW | Denied | It appears there are no fire hydrants anywhere close to the new building. The Fire Department requires either a fire hydrant within 300' of all parts of the building, or installation of fire sprinklers. Please indicate on drawings how fire protection requirements will be satisfied. |
01/27/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
01/29/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/02/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
02/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
02/13/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the route, slope, and connection point of the new building sewer to the existing private sewer collection system. Reference: Section 103.2.3, UPC 2006. 2. All plumbing fixtures and fittings shall be listed or labeled by a nationally-recognized, accredited conformity assessment company (e.g. UL, ETL, UPC, etc). Reference: Section 301.1.1, UPC 2006. 3. Show the materials for the new water service and water distribution piping and for the new building sewer and drain piping. Reference: Section 103.2.3, UPC 2006. 4. Provide cleanouts sized per Section 707.11, UPC 2006. |
02/13/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
02/17/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T08CM03793 4133 N STONE ADDITION GARAGE AND CRAFT ROOM The electrical plans have been denied for the following: 1. Per section 225-30 and 31 of the 2005 NEC, a main disconnect is required at the seperate structure. The panel would be allowed to have only six circuit breakers, the panel shown has more than six, therefore it requirs a main. 2.Section 250-32 of the NEC requires this structure to have it's own grounding system, include one in drawing and size. 3.Provide information on outside fixtures, cut sheet showing cut off, lamp type and lumen output. This is in order to verify compliance with City/County Outdoor Lighting ord # 10135. 4.Show location of existing 400 amp service, also provide load on this service and add new load to verify total. Ray T Majuta DSD City of Tucson Electrical Plan Ck 2/18/09 520-873-4899 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/20/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
02/20/2009 | SUE REEVES | REJECT SHELF | Completed |