Permit Number: T08CM03770
Parcel: 12801005H

Review Status: Active

Review Details: CELL TOWER/ANTENNAS

Permit Number - T08CM03770
Review Name: CELL TOWER/ANTENNAS
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2008 MARTIN BROWN FIRE REVIEW Approved
12/01/2008 STEVE SHIELDS ZONING REVIEW Approved
12/01/2008 Michael Wyneken PLANNING-CITY HALL REVIEW Approved
12/02/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL FOR 3/32" LETTERING IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING.
12/04/2008 JAY HOGAN COMMUNICATIONS REVIEW Approved
12/15/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:5870 E Broadway Bl
AT&T Cell Site
T08cm3770


The electrical plans for this project have been denied for the following items:

1. Electrical plans must be sealed and dated by EE.
2. Provide fault current values at main disconnect and at power cabinet.
3. Comply with section 230 of the NEC 2006, for location and grouping of the service as compared with other services on the building.
4. Determine if isolation transformer is to be installed , and if to be installed provide information on plan for it.

Ray T Majuta
Electrical Plan Check
Dsd City of Tucson
520-837-4988
12-16-08
12/15/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/17/2008 GERARDO BONILLA REJECT SHELF RECEIVED