Permit Review Detail
Review Status: Active
Review Details: CELL TOWER/ANTENNAS
Permit Number - T08CM03770
Review Name: CELL TOWER/ANTENNAS
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/01/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/01/2008 | Michael Wyneken | PLANNING-CITY HALL | REVIEW | Approved | |
| 12/02/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL FOR 3/32" LETTERING IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING. |
| 12/04/2008 | JAY HOGAN | COMMUNICATIONS | REVIEW | Approved | |
| 12/15/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:5870 E Broadway Bl AT&T Cell Site T08cm3770 The electrical plans for this project have been denied for the following items: 1. Electrical plans must be sealed and dated by EE. 2. Provide fault current values at main disconnect and at power cabinet. 3. Comply with section 230 of the NEC 2006, for location and grouping of the service as compared with other services on the building. 4. Determine if isolation transformer is to be installed , and if to be installed provide information on plan for it. Ray T Majuta Electrical Plan Check Dsd City of Tucson 520-837-4988 12-16-08 |
| 12/15/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/17/2008 | GERARDO BONILLA | REJECT SHELF | RECEIVED |