Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03738
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/11/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the building addition complies with the current code (2006 IECC). There is insufficient information for the windows and the entrance door to evaluate the addition. 2. Provide balancing information for the new rooftop unit that indicates how much outside air is being supplied to the new addition. 3. To prevent recirculation of the air from the restrooms, the exhaust fans shall operate whenever the rooftop unit is supplying air to the restrooms. |
06/11/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Reference 707.4 2006 UPC Each horizontal drainage pipe shall be provided with a clean-out at its upper terminal. |
06/26/2009 | GBONILL1 | ZONING | REVIEW | Needs Review | |
06/26/2009 | GBONILL1 | ENGINEERING | REVIEW | Needs Review |