Permit Number: T08CM03738
Parcel: 13628005S

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03738
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the building addition complies with the current code (2006 IECC). There is insufficient information for the windows and the entrance door to evaluate the addition.
2. Provide balancing information for the new rooftop unit that indicates how much outside air is being supplied to the new addition.
3. To prevent recirculation of the air from the restrooms, the exhaust fans shall operate whenever the rooftop unit is supplying air to the restrooms.
06/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Reference 707.4 2006 UPC Each horizontal drainage pipe shall be provided with a clean-out at its upper terminal.
06/26/2009 GBONILL1 ZONING REVIEW Needs Review
06/26/2009 GBONILL1 ENGINEERING REVIEW Needs Review