Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T08CM03732
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/20/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 11/20/2008 | Michael Wyneken | ZONING-CITY HALL | REVIEW | Approved | |
| 11/21/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/24/2008 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/28/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: PROVIDE CALCULATION FOR ADEQUACY OF EXISTING FLOOR SLAB WITH NEW GENERATOR/CONTAINMENT LOAD. 2. GENERAL: PROVIDE CALCULATION FOR ADEQUACY OF EXISTING ROOF FRAMING WITH NEW MUFFLER LOAD (1" GAP BETWEEN EXISTING JOISTS AND NEW JOISTS). 3. SHEET S-1 (WALL FRAMING PLAN); DETAIL 2/S-5: PROVIDE STRUCTURAL CALCULATIONS ALONG WITH A HEADER DETAIL FOR THE NEW 36" X 36" OPENING IN THE EXISTING PRECAST CONCRETE WALL. 4. SHEET S-5: PROVIDE DETAIL FOR NEW PENETRATION THROUGH EXISTING ROOF. |
| 12/04/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/15/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/15/2008 | SUE REEVES | REJECT SHELF | Completed |