Permit Number: T08CM03732
Parcel: 11921053G

Address:
1580 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T08CM03732
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/20/2008 Michael Wyneken ZONING-CITY HALL REVIEW Approved
11/21/2008 MARTIN BROWN FIRE REVIEW Approved
11/24/2008 STEVE SHIELDS ZONING REVIEW Approved
11/28/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE CALCULATION FOR ADEQUACY OF EXISTING FLOOR SLAB WITH NEW GENERATOR/CONTAINMENT LOAD.
2. GENERAL: PROVIDE CALCULATION FOR ADEQUACY OF EXISTING ROOF FRAMING WITH NEW MUFFLER LOAD (1" GAP BETWEEN EXISTING JOISTS AND NEW JOISTS).
3. SHEET S-1 (WALL FRAMING PLAN); DETAIL 2/S-5: PROVIDE STRUCTURAL CALCULATIONS ALONG WITH A HEADER DETAIL FOR THE NEW 36" X 36" OPENING IN THE EXISTING PRECAST CONCRETE WALL.
4. SHEET S-5: PROVIDE DETAIL FOR NEW PENETRATION THROUGH EXISTING ROOF.
12/04/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/15/2008 DELMA ROBEY OUT TO CUSTOMER Completed
12/15/2008 SUE REEVES REJECT SHELF Completed