Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03714
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/16/2009 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/16/2009 | RONALD BROWN | ADA | REVIEW | Passed | NOT A COT OWNED/OPERATED PROPERTY |
| 07/16/2009 | DAVE MANN | FIRE | REVIEW | Denied | Provide Code Review Checklist for project. Provide sealed drawings. Show fire walls for property lines. Enclosed area cannot exit across property line. |
| 07/17/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT: PROVIDE MAXIMUM 20% OF BUDGET COSTS FOR ACCESSIBILITY UPGRADES. SHOW THIS CALCULATION ON THE PLANS. 2. PREVIOUS COMMENT: ADDRESS THE FIRE RATED WALL ADJACENT TO THE LOT SPLIT PROPERTY LINE. SHOW THIS ON THE PLANS. 3. PREVIOUS COMMENT: PROVIDE REGISTRANT SEAL ON THE ELECTRICAL DRAWINGS. 4. PREVIOUS COMMENT: PROVIDE COMPLETE FLOOR PLAN WITH REGISTRANT SEAL. 5. PREVIOUS COMMENT: PROVIDE HVAC VENTING CALCULATIONS FOR THE NEW ENCLOSURE, SEALED BY THE REGISTRANT. 6. PREVIOUS COMMENT: PROVIDE SWINGING ACCESS DOORS TO THE NEW CONFERENCE ROOM. SLIDING DOORS GOOD FOR RESIDENTIAL ONLY. 7. PREVIOUS COMMENT: PROVIDE NEW OCCUPANCY CODE ANALYSIS. 8. PREVIOUS COMMENT: PROVIDE PLUMBING FIXTURE COUNT TO NEW OCCUPANCY. 9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL COMMENTS IN THIS REVIEW. 10. GENERAL: PROVIDE TWO COPIES OF STRUCTURAL CALCULATIONS FOR REVIEW. |
| 07/20/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | 1. SEE BUILDING COMMENTS. |
| 07/21/2009 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 07/24/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide roof drainage calculations and plans for the addition. Reference: Section 1101.11, UPC 2006. |
| 07/24/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/24/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide construction documents drawn to scale and with sufficient detail and clarity to demonstrate that the work complies with the applicable codes. Reference: Section 106.1.1, IBC 2006. 3. Provide energy code compliance calculations for the addition to the building. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006. 4. Provide sufficient heat for the addition to maintain a minimum temperature of 68 F on a design heating day (32 F). Reference: Section 309.1, IMC 2006. 5. Provide calculations demonstrating adequate ventilation for the addition. Reference: Section 401.2, IMC 2006. 6. Revise the plans as required to show that any intake openings (e.g. doors and operable windows) are at least 10 feet from property lines or parking lots. Reference: Section 401.4, IMC 2006. |
| 08/03/2009 | BIANCA RAMIREZ | ENGINEERING | REVIEW | RECEIVED | 1. Engineering is unable to approve plans until all other department comments have been addressed. 2. Once all required documentation has been submitted, Engineering will re-review. 3. Additional comments may be forthcoming. If you have any further questions, please contact me at bianca.ramirez@tucsonaz.gov or 520-837-4928. Bianca Ramirez, CFM Engineering Associate |
| 08/05/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT: 444 W Ajo T08CM03714 Porch to Office Electrical, previous Building Review has requested drawings to be sealed by a Registrant. Ray T Majuta Electrical Plan Check DSD City of Tucson 8/6/09 520-837-4988 |
| 08/07/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/25/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/25/2009 | SUE REEVES | REJECT SHELF | Completed |