Permit Number: T08CM03711
Parcel: 11616302A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03711
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2008 MARTIN BROWN FIRE REVIEW Approved
11/20/2008 RONALD BROWN ZONING HC SITE REVIEW Passed THIS IS A COT PROJECT
11/20/2008 RBROWN1 ADA REVIEW Denied 20 NOVEMBER 2008
T08CM03711/HERRERA QUIROZ BASKETBALL COURT
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
ADAAG

DENIED: SEE COMMENTS BELOW

I. SHEET G0.0
A. CHANGE GOVERNING ACCESSIBILITY CODE TO ADAAG 1994 EDITION ONLY.

II. SHEET A2.0
B. PROVIDE A LARGE SCALE DETAIL OF THE ACCESSIBLE AND COMPANION SEATING COMPLYING WITH ADAAG SECTIONS 4.1.3 (19) AND 4.33.

END OF REVIEW
11/21/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING.
2. LIST SPECIAL INSPECTIONS REQUIRED FOR THIS PROJECT PER IBC SECTION 106.1.
3. CALCULATIONS SHEET 1 (SOIL); SHEET S0.1 (FOUNDATIONS): IBC TABLE 1804.2 (2006 IBC) FOR ALLOWABLE FOUNDATION PRESSURE HAS BEEN AMENDED BY THE CITY OF TUCSON SECTION 1805.2 'DEPTH OF FOOTINGS' TO READ: "THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES FOR 1000 PSF MAXIMUM ALLOWABLE FOUNDATION PRESSURE AND A MINIMUM 18 INCHES FOR MAXIMUM ALLOWABLE FOUNDATION PRESSURE VALUES OF TABLE 1804.2". REVISE CALCULATIONS AND DRAWINGS AS REQUIRED.
4. SHEET S0.1; POST TENSIONED SLAB ON GRADE: UNDER #1, SELECT BASIS OF DESIGN. SECTION 1805.8 ONLY DEALS WITH EXPANSIVE SOILS.
5. SHEET S0.1; LOADS: PROVIDE ROOF UPLIFT WIND LOAD.
6. SHEET A1.0 (SITE PLAN KEYNOTE 5); SHEET S2.0: KEYNOTE 5 INDICATES BLEACHER ANCHORING BY STRUCTURAL. DID NOT LOCATE ANCHORS ON PLANS. PROVIDE.
11/26/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the scupper opening in the rainwater collector boxes to a minimum of 4" per Section 1101.11.2.1, UPC 2006.
12/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/01/2008 ROBERT SHERRY WATER REVIEW Passed
12/02/2008 GERRY KOZIOL WWM REVIEW Passed
12/16/2008 LOREN MAKUS ENGINEERING REVIEW Approved