Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03694
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/17/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for the revised restroom per Section 403.3, IMC 2006 (75 CFM per water closet or urinal). |
| 11/17/2008 | ENEWCOM1 | ADA | REVIEW | Passed | |
| 11/17/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/17/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/17/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide upper terminal cleanouts per Section 707.4, UPC 2006. 2. Provide a riser diagram for the water supply to the fixtures. 3. Proviode a specification for the new fixtures. |
| 11/17/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/17/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 11/19/2008 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 11/19/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/19/2008 | CAGUILA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |