Permit Number: T08CM03690
Parcel: 11623063C

Address:
960 S FREEWAY

Review Status: Active

Review Details: RESUBMITTAL - SITE

Permit Number - T08CM03690
Review Name: RESUBMITTAL - SITE
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2009 TERRY STEVENS ZONING REVIEW Approved
03/25/2009 RONALD BROWN ZONING HC SITE REVIEW Denied 1. Sheet G1:
a. The governing accessible code is: 2006 IBC, Chapter 11, ICC/ANSI 117.1 2203 Edition. Please revise all ADA, ADAAG code references on all sheets to this code.
b. Clear width for all accessible pedestrian routes as required by Zoning Development Standards is 4' wide.
SHEET AS1.1
2. Note 204 references installing a new 4' wide concrete sidewalk flush with the asphaltic paving connection all the accessible spaces. From inspection of aerial photos, this work has already been completed. Provide information (spot grades) confirming compliance with ICC/ANSI 403.3, slope requirements.
3. For existing areas now deemed as accessible routes, please provide spot grade elevations at all of these areas sufficient to show compliance with Sections 403.3 Accessible Route Slopes.
4. Note 207 refers to installing a new concrete sidewalk level change. Please provide a large scale detail of this sloped area showing compliance with Section 403.3 and/or if slope is proven to be more than 5% show detail compliance with section 405, Ramps.
5. There is a line drawn between the accessible route and the swimming pool wrought iron fence line. What is this area?
6. Note 204 references a new 4' wide side walk be extended from this line to the gate entrance of the pool. Please provide a large scale detail confirming what the material is (as requested in note 5 defined above), the new 4' wide concrete walkway and both slope compliance (spot grades) with Section 403.3.
7. Please confirm slope of exiting curved accessible route access to the West end of the marked crossing
8. Please provide slope compliance of new concrete marked crossing.
9. Please confirm connection of parking aisle/marked crossing to the Public Right of Way pedestrian way at Frontage Road.
10. The location of all Accessible Parking spaces are existing and acceptable.
04/07/2009 JASON GREEN ENGINEERING REVIEW Denied DATE: April 8, 2009
SUBJECT: 960 S Freeway Site Plan- 2nd Engineering Review
TO: MPE Attn: Lisa Bowers
LOCATION: T14S R13E Sec14 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T08CM03690 (Site Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan (T08CM03690) for the above referenced property. Engineering Division does not recommend approval of the site plan application at this time. The following items need to be addressed:

SITE PLAN COMMENTS:

1) Complied.

2) Complied.

3) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all handicap and ANSI Standard requirements that apply to this project.

4) Complied.

5) Complied.

6) Acknowledged.


GENERAL COMMENTS:

Please provide a revised site plan that addresses handicap and ANSI comments per Ron Brown, RA. For expedite purposes the site plan can be reviewed over the counter (DSD Engineering Division comment only) for stamp approval once all items have been addressed. Provide the site plan with ANSI stamped approval prior to setting up a meeting for Engineering counter approval.

For questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services