Permit Number: T08CM03688
Parcel: 11808009B

Address:
1222 S FREEWAY

Review Status: Completed

Review Details: SITE

Permit Number - T08CM03688
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2008 MARTIN BROWN FIRE REVIEW Approved
11/21/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
11/21/2008 TERRY STEVENS ZONING REVIEW Denied 1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the areas of revised accessibility.

2. Zoning acknowledges the receipt of an approved site plan. This plan does not show the parking area expansions to the north and south. Provide documentation that approves this expansion. If unable to provide the expansion documentation a new site plan is required meeting D.S. 2-02 requirements. It appears that the expansion may require full code compliance due to a greater than twenty-five (25) percent expansion. If documentation is provided that approved this expansion, a site plan review is still required for the parking re-strip. The parking re-strip site plan requires a fully dimensioned parking layout and is a separate review from the proposed tenant improvement. Due to the proposed restriping of existing parking a site review is required. Submit a site plan showing all fully dimensioned parking layout for site review. Include the proposed ADA changes. Provide a copy of the last approved site plan with this submittal.

3. D.S. 2-02.2.1.8 North of the existing trash area there are ten (10) vehicle parking spaces called out with only nine (9) shown, please clarify.

4. D.S. 2-02.2.1.8 South of the existing trash area there are six (6) vehicle parking spaces called out, the western most vehicle parking space does not meet minimum width requirements or the maneuvering requirements. See D.S. 305.2.1.B.1 and D.S. 3-05.2.2.D.

5. D.S. 2-02.2.1.12 It is not clear how the proposed sidewalk and truncated domes works with the proposed accessible route located near the northwest corner of the building. Is this sidewalk flush with pavement or raised? Is there a ramp?

6. D.S. 2-02.2.1.12 It appears that the proposed crosswalk that will connect the pool to the hotel encroaches into the twenty-four (24) foot parking area access lane (PAAL). Provide a dimension for the PAAL to the north. Per D.S. 3-05.2.1.C.1 the minimum width of a two-way PAAL is twenty-four (24) feet.

7. D.S. 2-02.2.1.12 The proposed crosswalk that connects the pool to the hotel, north end is required to be a sidewalk, physically separated from the PAAL and parking spaces, the depth of the parking space area.
11/21/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 1. THE ACCESSIBLE CROSSING AT SOUTH END DOES NOT WORK BEING IN THE VEHICLE WAY. MOVE THE SOUTH ENTRANCE FOR THE MARKED CROSSING ROUTE TO THE EAST SO AS TO BE PARALLEL AND DIRECTLY ACCESSIBLE WITH THE EXISTING CONCRETE WALKWAY ACCESSIBLE ROUTE.
2. PROVIDE LARGESCALE DETAILS OF BOTH ENDS OF ACCESSIBLE ROUTE AND OF WHAT APPEARS MAY BE A RAMP. SHOW ALL DIMS, SLOPES, MATERIAL FINISHES, RAMPS AND DETECTABLE WARNINGS REQUIRED BY ICC/ANSI SECTIONS 405 AND 406.
3. PROVIDE SPOT GRADES ALONG ALL NEW ACCESSIBLE ROUTES OR OTHERWISE INDICATE SLOPE COMPLIANCE WITH ICC/ANSI 117.1, SECTION 403.3
2. AT NOTE 205, PLEASE PROVIDE SPOT GRADES TO SHOW CODE COMPLIANCE, ICC SECTION 403.3.
3. DETAIL 8/AS1.2, OPTION "A": IF USED REFERENCE ZONING COMMENTS FOR ACCESSIBLE ROUTE AND PAAL SEPARATION REQUIREMENTS AND LOCATE SIGNAGE.
4. REFERENCE "PARK WISE" FOR ACCESSIBLE PARKING SIGNAGE. CONTACT DAN ANGEL, 429-3318.
5. BOTTOM OF MAIN ACCESSIBLE SIGNAGE TO BE 74".
12/03/2008 PETER MCLAUGHLIN LANDSCAPE REVIEW Passed
12/03/2008 PETER MCLAUGHLIN NPPO REVIEW Passed
12/03/2008 JASON GREEN ENGINEERING REVIEW Denied DATE: December 3, 2008
SUBJECT: 1222 S Freeway Site Plan- Engineering Review
TO: MPE Attn: Lisa Bowers
LOCATION: T14S R13E Sec23 Ward 1
REVIEWERS: Jason Green, CFM
ACTIVITY: T08CM03688 (Site Plan)

SUMMARY: Engineering Division of Development Services Department has received and reviewed the site plan (T08CM02132) for the above referenced property. Engineering Division does not recommend approval of the site plan application at this time. The following items need to be addressed:

SITE PLAN COMMENTS:

1) DS Sec.2-02.2.1.A.8: Revise the site plan to label and dimension the existing vehicular use area (north and south side of building) to verify conformance with the minimum requirements of DS Sec.3-05. Or provide a copy of the last approved site plan that shows the existing vehicular use areas to be in conformance with the Development Standards.

2) DS Sec.2-02.2.1.A.8: Revise the site plan to dimension the minimum 24-foot PAAL widths for all two-way traffic (12-foot for one-way traffic unless used as a Fire Access Lane then 20-foot minimum) at all locations on the site plan. All driveway entrances must also meet the minimum 24-foot width requirements for 2-way traffic.

3) DS Sec.2-02.2.1.A.8: Revise the site plan to verify that all existing parking spaces are labeled and shown and that they meet the minimum width requirements or the maneuvering requirements of DS Sec.305.2.1.B.1 and DS Sec.3-05.2.2.D.

4) DS Sec.2-02.2.1.A.12: Refer to comments from Ron Brown, RA Structural Plans Examiner for all handicap and ANSI Standard requirements that apply to this project.

5) DS Sec.2-02.2.1.A.12: Revise the site plan to clarify how the proposed sidewalk and truncated domes functions with the proposed accessible route located near the northwest corner of the building.

6) DS Sec.2-02.2.1.A.12: Revise the site plan to label and dimension all parking area access lanes (PAAL). Per DS Sec.3-05.2.1.C.1 the minimum width of a two-way PAAL is 24 feet. It appears that the proposed crosswalk that will connect the pool to the hotel encroaches into the 24-foot PAAL and the PAAL on the north parking lot is only 23 feet 1 inch, revise.

7) DS Sec.2-02.2.1.A.12: Revise the site plan to show that the proposed pedestrian crosswalk that connects the pool to the hotel is physically separated from the PAAL and parking spaces by a vertical curb, wheel stops or bollards.

8) Be advised that further comments may be forth coming on resubmittal of the site plan, specifically if the Zoning Departments determines that the site plan must meet full code compliance due to expansion.

GENERAL COMMENTS:

Please provide a revised site plan that addresses the comments provided above. Include a comprehensive response letter addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package.

Further comments may be generated upon resubmittal of the site plan review.

If you have any questions or to schedule an appointment I can be reached at 837-4929.




Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services
12/23/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2008 GERARDO BONILLA OUT TO CUSTOMER Completed
12/23/2008 GERARDO BONILLA REJECT SHELF Completed