Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03683
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
11/14/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
11/17/2008 | ENEWCOM1 | ADA | REVIEW | Passed | |
11/17/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006. 2. Show that a separation of at least ten feet exists between air intake openings and exhaust openings. Reference: 401.4.1, IMC 2006. 3. Provide the balancing and equipment specifications for EF-1. Reference: Sections 106.3.1 and 403.3, IMC 2006. 4. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006. 5. Provide smoke detectors in the return air duct, upstream of any outside air connections, for all air distribution systems with a capacity greater than 2,000 CFM. Reference: Section 606.1, IMC 2006. 6. Floor drains used as indirect receptors for condensate are required to be designed to prevent splashing (e.g. equipped with a funnel top) but indirect waste receptors shall not be installed in a restroom. See Section 307.2.2, IMC 2006, as amended by the City of Tucson for allowable terminations for condensate drains. Reference: Section 804.1, UPC 2006. 7. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson. |
11/17/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. MINIMUM 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS. APPEAL MUST BE MADE TO THE BUILDING OFFICIAL, JESSIE SANDERS, FOR 3/32" LETTERING. AN APPROVED APPEAL MUST BE INCLUDED WITH THE PLANS FOR REVIEW. 2. WALL TYPE 3 ON SHEET A2.1: SHOW THE INTERIOR WALL BRACE/CONNECTION TO THE STRUCTURE ABOVE AND THE CONNECTION AT THE BASE OF THE WALL FOR LOADS FROM IBC 1607.13. 3. 6/A3.2: BRACE THE BOTTOM CHORDS OF THE STRUCTURAL JOISTS TO ADJACENT JOISTS TOP CHORD WHERE HANGERS OCCUR. GIVE UNISTRUT SIZE. 4. CALCULATIONS ARE REQUIRED FOR THE ADEQUACY OF EXISTING ROOF JOISTS AT THE LOCATION OF THE NEW ROOF TOP UNIT. SHOW SUPPORT MEMBER SIZES AND CONNECTIONS. |
11/17/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). (A 3/32" font may be allowed with an appeal to the building official.) Reference: Section 106.1.1, IBC 2006. 2. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference: Section 402.1, UPC 2003, as amended by the State of Arizona. 3. Provide an expansion tank or other approved device for controlling thermal expansion for storage-type water heaters. Reference: Section 608.3, UPC 2006. 4. Provide a temperature/pressure relief valve for the water heater. Reference: Sections 103.2.3, 505.4, 505.5, 608.3, and 608.4 UPC 2006. |
11/17/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
11/18/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
11/18/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Denied for following ; 1. Min 1/8" lettering required on all drawings. Ray T Majuta Elect PLan Ck DSD Tucson Az, 11/18/08 520-8374988 |
12/11/2008 | CPIERCE1 | WWM | REVIEW | Needs Review | |
12/11/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |