Permit Number: T08CM03663
Parcel: 117050810

Address:
305 N HERBERT AV

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM03663
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2008 DAVE MANN FIRE REVIEW Approved
11/14/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL FOR 3/32" LETTERING IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY THE DRAWINGS SUBMITTED FOR CHECKING.
2. SHEET A-2; DETAIL 5: REMOVE THE QUESTION MARK FROM THE CONCRETE FOOTING PLAN AND SECTION.
12/01/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Poject: 305 N Herbert, New Sculpture
T08CM03663

This project has been denied for the following items,

1. The 2005 City of Tucson/Pima County Outdoor Lighting Code under Section 3.2 Minor Additions states, "Any new lighting on site shall meet the requirements of this code with regard to shielding and lamp type; the total amount of lighting after modifications are complete shall not exceed that on site before the modification, or that permitted by this code, whichever is larger."
Describe the type of fixture to be used including the lumen output per each and total, also if these are shielded or not, if not do they comply with the ordinance.



Ray T Majuta
DSD Elect Plan Ck
City of Tucson
520-837-4988
12/01/08

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2008 SUE REEVES APPROVAL SHELF Completed
12/03/2008 CINDY AGUILAR OUT TO CUSTOMER Completed