Permit Number: T08CM03607
Parcel: 12620001C

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM03607
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/12/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: 3400 E Camino Campestre
T08CM03607

The Electrical Plans for this project have been denied for the following items; provide response for individual items and indicate actions taken to resolve them.


1.Will all pull boxes be required to be replaced? If so how is the determination made to use either a #3 , 5, or a #7, the Construction Documents state the different sizes.

2.The detail on Sheet 7.0 shows a ground rod installed in the pull box, how is the connection to this rod to be made and to which conductors will they be connected to. Note on plan.

3. Sheet E-3.0 on the feeder run between P-17c to P-18c, the circuit contains only one neutralwhile all other feeders contain two. Please list your requirement for the running of two neutrals.

4. Sheet E-3.0 under the Field 4 grouping of pole feeders, P-8c and P-7c are listed, they do not belong in this group, I beleive they belong to Field 1 group.

5. Sheet E-3.0 under the Field 4 grouping P-21c and P-22c are missing.

6. Sheet E-3.0 under Field 4 grouping the following are shown twice P-14a and P-13a, while P-19c and P-20c are missing. Also P-16a and P-15b should be in this group.

7. The feeder for P-7c and P-8c show P-7b and P-8a , and P-14b and P-13b are shown twice.



Ray T Majuta
DSD City of Tucson
Electrical Plan Check
11/10/08
520-837-4988

Final Status

Task End Date Reviewer's Name Type of Review Description
11/13/2008 DELMA ROBEY OUT TO CUSTOMER Completed
11/13/2008 SUE REEVES REJECT SHELF Completed