Permit Number: T08CM03588
Parcel: 10306092G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03588
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/18/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. CALCULATIONS FOR CONTROL BUILDING, PAGE 9; SHEET 7 OF 17: CALCULATIONS CALL FOR 1-#5 AT WALL ENDS, WHILE NOTE 9 ON SHEET 7 CALLS FOR #4. CLARIFY.
2. SHEET 7 OF 17; SHEET 8 OF 17: NOTE 1 UNDER "FOUNDATION AND EARTHWORK" ON SHEET 8 LISTS SOIL BEARING PRESSURE AS 1500 PSF AT 1'-6" DEPTH BELOW GRADE, BUT SECTION C ON SHEET 7 SHOWS BOTTOM OF FOOTING AT 12" DEPTH (PER IBC CITY OF TUCSON AMENDMENTS, SECTION 1805.2, ALLOWABLE SOIL BEARING PRESSURE AT 12" IS 1000 PSF). CLARIFY.
3. SHEET 14 OF 17; RADIO ANTENNA SECTION 1: IS FOUNDATION TO BE 18" SQUARE (PER DRAWINGS) OR 18" DIAMETER (PER CALCULATIONS? CLARIFY.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/20/2008 VFLORES1 OUT TO CUSTOMER Completed
11/20/2008 SUE REEVES REJECT SHELF Completed