Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03588
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/18/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. CALCULATIONS FOR CONTROL BUILDING, PAGE 9; SHEET 7 OF 17: CALCULATIONS CALL FOR 1-#5 AT WALL ENDS, WHILE NOTE 9 ON SHEET 7 CALLS FOR #4. CLARIFY. 2. SHEET 7 OF 17; SHEET 8 OF 17: NOTE 1 UNDER "FOUNDATION AND EARTHWORK" ON SHEET 8 LISTS SOIL BEARING PRESSURE AS 1500 PSF AT 1'-6" DEPTH BELOW GRADE, BUT SECTION C ON SHEET 7 SHOWS BOTTOM OF FOOTING AT 12" DEPTH (PER IBC CITY OF TUCSON AMENDMENTS, SECTION 1805.2, ALLOWABLE SOIL BEARING PRESSURE AT 12" IS 1000 PSF). CLARIFY. 3. SHEET 14 OF 17; RADIO ANTENNA SECTION 1: IS FOUNDATION TO BE 18" SQUARE (PER DRAWINGS) OR 18" DIAMETER (PER CALCULATIONS? CLARIFY. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/20/2008 | VFLORES1 | OUT TO CUSTOMER | Completed |
| 11/20/2008 | SUE REEVES | REJECT SHELF | Completed |