Permit Number: T08CM03574
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T08CM03574
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/18/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
08/19/2009 BIANCA RAMIREZ ENGINEERING REVIEW Approved
08/26/2009 STEVE SHIELDS ZONING REVIEW Approved
09/10/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied 1. See sheet P-1.2, relocated storm drain, next to equipment room 106. Attached note says "Provide new 6" storm drain leader for new roof downspout location. Daylight to grade. Verify location on architectural plan." Currently there is installed a 6" PVC rainwater leader which dumps onto the roof above room 107. Is this a temporary installation, or if it is part of the final design, incude it in your drawing, with all revised calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/02/2009 CPIERCE1 OUT TO CUSTOMER Completed
10/02/2009 SUE REEVES REJECT SHELF Completed