Permit Number: T08CM03574
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T08CM03574
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2009 MARTIN BROWN FIRE REVIEW Approved
06/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE THE LATEST SET OF APPROVED DRAWINGS ALONG WITH THIS REVISED SET.
2. SHEET A7.04: IS THIS A NEW SHEET? IT IS NOT REFERENCED IN THE DRAWING INDEX ON THE TITLE SHEET TS1.01. CLARIFY.
3. STRUCTURAL CALCULATIONS: IS THE EQUIPMENT PLATFORM MEZZANINE FRAMING PLAN REVISED? THE CALCULATIONS INDICATE IT IS. SEE NOTE 1.
06/22/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Costco - 6255 E. Grant Road
T08CM03574-R
Building Plan - 2nd Revision (1st Review)

TRANSMITTAL DATE: June 22, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning acknowledges that a revised development plan has been submitted. Until the revised development plan has been approved the Zoning Review section will not be able to approve the building plans.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped revised development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm03574-2ndR.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/23/2009 BIANCA RAMIREZ ENGINEERING REVIEW Denied DSD TRANSMITTAL

FROM: Bianca Ramirez, CFM
Engineering Associate

PROJECT: Costco - 6255 E. Grant Road
T08CM03574-R
Building Plan - 2nd Revision (1st Review)

TRANSMITTAL DATE: June 23, 2009

1. The building plan has been reviewed by the Engineering Section but cannot approve the plan until all the Development plan comments and/or concerns have been addressed.

2. Zoning acknowledges that a revised development plan has been submitted. Until the revised development plan has been approved the engineering and zoning sections, the engineering section will not be able to approve the building plans.

3. Engineering will re-review the building plan on the next submittal to insure compliance with the approved and stamped revised development plan.

4. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Bianca.Ramirez@tucsonaz.gov or (520) 837-4928
06/26/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved construction plans for comparison with the revised plans. Cloud all of the changes that have been made to the approved plans; not just the "owner revisions" issue. Reference: Section 103.2.3, UPC 2006.
2. Revise the overflow drain to include a strainer (Detail 4/7.01). Reference: Section 1105.2, UPC 2006.
3. Show how the roof of the mechanical room (106) is to be drained or provide structural calculations to show that the roof can support the weight of water that will accumulate with no roof drain. Reference: Section 1611.1, IBC 2006.
4. Revise the weir overflow shown in the roof conductor head (detail 4/A2.02) to have the same capacity as the scupper. Reference: Section 1101.11.2, UPC 2006.
06/26/2009 ROBERT SHERRY WATER REVIEW Approved
06/26/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved construction plans for comparison with the revised plans. Cloud all of the changes that have been made to the approved plans; not just the "owner revisions" issue. Reference: Section 106.3.1, IMC 2006.
2. Condensate drains may not terminate over or into a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage (Detail 81/P-4.1). Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
06/30/2009 GERRY KOZIOL WWM REVIEW Passed
07/10/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; 6255 E GRANT RD
T08CM03574
Costco Revisions


The Electrical Plans have been denied for the following;

1. Provide a copy of the previously approved plans in order to compare the existing with the new revised.


Ray T Majuta, Elect Plan CK
PDS, City of Tucson,
7/11/09,
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2009 CPIERCE1 OUT TO CUSTOMER Completed
07/30/2009 SUE REEVES REJECT SHELF Completed