Permit Number: T08CM03574
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03574
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: Costco Remodel
6255 E Grant Rd
T08CM03574


Electrical Plans have been denied for the following items, address each individually and indicate how each has been addressed.

1. New Sheets have been introduced which were missing in the first review, now new Sheets R2a,r2b and R2c indicate changes which have not made to the existing Electrical Sheets. Sheet R2c introduces changes in Panel schedules for H3, H5 and P3 and P5. These changes are not noted on the E-Panel schedules.
2. New Sheet R2c shows a new panel H3, sheet E-6 only shows panels H3-1 and H3-2. New panel H3 on R2c sheet shows circuits for compressor racks C and D. In Sheet E-6 Panel H3-1 shows compressor rack C, and Panel H3-2 shows compressor rack D.
Note single line diagram does not show a Panel H3, only
H3-1 and H3-2.
3. Sheet E-1 shows Pnl P-2 as a two section panel, the panel schedule shows only one section panel.
4. Sheet E-1 shows Pnl P-1 a one section panel, Sheet E-6 shows a two section panel.



Ray T Maajuta
DSD City of Tucson
Elect Plan Ck
520-837-4988
3/23/09
03/20/2009 GERRY KOZIOL WWM REVIEW Denied needs to build public sewer, needs hold harmless letter
03/23/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/26/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Costco - 6255 E. Grant Road
T08CM03574
Building Plan (3rd Review)

TRANSMITTAL DATE: March 26, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning acknowledges that a revised development plan will be submitted. Until a revised development plan has been submitted and approved the Zoning Review section will not be able to approve the building plans. At the southwest corner of the proposed Receiving addition there is a pump room shown. This pump room is not shown on the approved development plan. If this pump room is to remain as part of this project a revised development plan is required.

3. On the approved development plan at the southwest corner of the proposed Receiving addition there was a required sidewalk shown between the proposed addition and the loading space, on the submitted building plans this sidewalk has been removed. The development plan and building plans should match. Until on or the other has been revised the building plan cannot be approved.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm03574.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development plan and additional requested documents
03/27/2009 ROBERT SHERRY WATER REVIEW Approved
03/27/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
03/27/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/03/2009 CPIERCE1 OUT TO CUSTOMER Completed
04/03/2009 SUE REEVES REJECT SHELF Completed