Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03574
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2009 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 02/18/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/20/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | COSTCO:EXPANSION/ REMODEL NEED WASTEWATER/ IWC REVIEW OF GREASE INTERCEPTOR- TOM TOMCHAK- 443-6200 - 5025 W INA |
| 03/04/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not resolved. Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project (114 GPM). Reference: Sections 610.2 and 610.12, UPC 2006. |
| 03/05/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify the adequacy of the roof framing at exhaust fans EF-11 and EF-12 based upon the structural requirement of a maximum fan weight of 75 pounds (sheet S2.2)compared to an actual fan weight of 142 pounds. Reference: Sections 302.1 and 507.6, IMC 2006. |
| 03/05/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The drain for the cooling tower, as it is shown on the revised drawings, is part of a mechanical system, not part of the sanitary drain system. Revise the labeling accordingly. Reference: Section 306.2, UPC 2006. 2. The vacuum relief valves shown for the water heaters and pre-heaters in detail 15/P-2.4 are not installed per their listing for water service; no valves are to be located between the vacuum relief valves and the storage tanks. Reference: Section 608.7, UPC 2006. 3. Comment not resolved; see the mechanical room/ maintenance room, fire pump room, receiving area (MS-2), and the fresh line (GW). Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. 4. The Arizona State Food Code requires that utensils and food-contact surfaces shall be sanitized after cleaning. If the multiple-compartment sinks (E-22 and E-23) are being used for dishwashing, verify if a sanitizing compartment with an indirect connection will be required in addition to the directly-connected wash and rinse compartments. Reference: Sections 304.0 and 801.2.3, UPC 2006. 5. Provide reference copies of civil sheet C-1.6 for review of the coordination the storm drainage and sewer designs shown on sheets P-1.2. Reference: Section 103.2.3, UPC 2006. 6. Detail 2/P-2.3 shows a 3" trap connected to a 2" tailpiece for floor drain D-1. A trap may be no larger than one pipe size larger than the required tailpiece. Reference: Table 7-3 and Section 1003.3, UPC 2006. |
| 03/09/2009 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Costco - 6255 E. Grant Road T08CM03574 Building Plan (2nd Review) TRANSMITTAL DATE: March 9, 2009 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning acknowledges that a revised development plan will be submitted. Until a revised development plan has been submitted and approved the Zoning Review section will not be able to approve the building plans. At the southwest corner of the proposed Receiving addition there is a pump room shown. This pump room is not shown on the approved development plan. If this pump room is to remain as part of this project a revised development plan is required. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t08cm03574.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 03/13/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PROJECT: T08CM03574 6255 E GRANT RD COSTCO REMODEL This electrical plan has been denied for the following items; 1. The request of previous comments dated 2-06-09, refer to items 12,13,14,15 and 16. Sheets R2A, R2B, and R2C are missing. These sheets are required to be submitted with these plans. Ray T Majuta DSD City of Tucson Elect Pl Ck 3-14-09 520-837-4988 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 03/19/2009 | SUE REEVES | REJECT SHELF | Completed |