Permit Number: T08CM03574
Parcel: 110162190

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03574
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
02/18/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/20/2009 GERRY KOZIOL WWM REVIEW Denied COSTCO:EXPANSION/ REMODEL
NEED WASTEWATER/ IWC REVIEW OF GREASE INTERCEPTOR- TOM TOMCHAK- 443-6200 - 5025 W INA
03/04/2009 ROBERT SHERRY WATER REVIEW Denied Comment not resolved. Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project (114 GPM). Reference: Sections 610.2 and 610.12, UPC 2006.
03/05/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Verify the adequacy of the roof framing at exhaust fans EF-11 and EF-12 based upon the structural requirement of a maximum fan weight of 75 pounds (sheet S2.2)compared to an actual fan weight of 142 pounds. Reference: Sections 302.1 and 507.6, IMC 2006.
03/05/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The drain for the cooling tower, as it is shown on the revised drawings, is part of a mechanical system, not part of the sanitary drain system. Revise the labeling accordingly. Reference: Section 306.2, UPC 2006.
2. The vacuum relief valves shown for the water heaters and pre-heaters in detail 15/P-2.4 are not installed per their listing for water service; no valves are to be located between the vacuum relief valves and the storage tanks. Reference: Section 608.7, UPC 2006.
3. Comment not resolved; see the mechanical room/ maintenance room, fire pump room, receiving area (MS-2), and the fresh line (GW). Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006.
4. The Arizona State Food Code requires that utensils and food-contact surfaces shall be sanitized after cleaning. If the multiple-compartment sinks (E-22 and E-23) are being used for dishwashing, verify if a sanitizing compartment with an indirect connection will be required in addition to the directly-connected wash and rinse compartments. Reference: Sections 304.0 and 801.2.3, UPC 2006.
5. Provide reference copies of civil sheet C-1.6 for review of the coordination the storm drainage and sewer designs shown on sheets P-1.2. Reference: Section 103.2.3, UPC 2006.
6. Detail 2/P-2.3 shows a 3" trap connected to a 2" tailpiece for floor drain D-1. A trap may be no larger than one pipe size larger than the required tailpiece. Reference: Table 7-3 and Section 1003.3, UPC 2006.
03/09/2009 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Costco - 6255 E. Grant Road
T08CM03574
Building Plan (2nd Review)

TRANSMITTAL DATE: March 9, 2009

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning acknowledges that a revised development plan will be submitted. Until a revised development plan has been submitted and approved the Zoning Review section will not be able to approve the building plans. At the southwest corner of the proposed Receiving addition there is a pump room shown. This pump room is not shown on the approved development plan. If this pump room is to remain as part of this project a revised development plan is required.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm03574.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
03/13/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied PROJECT: T08CM03574
6255 E GRANT RD
COSTCO REMODEL


This electrical plan has been denied for the following items;


1. The request of previous comments dated 2-06-09, refer to items 12,13,14,15 and 16. Sheets R2A, R2B, and R2C are missing. These sheets are required to be submitted with these plans.



Ray T Majuta
DSD City of Tucson
Elect Pl Ck
3-14-09
520-837-4988

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2009 CPIERCE1 OUT TO CUSTOMER Completed
03/19/2009 SUE REEVES REJECT SHELF Completed