Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03544
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/04/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 11/04/2008 | ENEWCOM1 | ADA | REVIEW | Passed | NOT A COT PROJECT |
| 11/04/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | DENIED BY RON BROWN 1. NEED A PERMIT FOR EACH ADDRESS. |
| 11/04/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Denied | DENIED BY RON BROWN 1. TOILET DO NOT MEEST ANSI STANDARDS FOR SPACE ENCROACHMENTS. |
| 11/06/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approv-Cond | The three (3) shipping containers must be removed before final inspection. |
| 11/07/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.PROVIDE THE SERVICE ENTRANCE CONDUCTORS AND CONDUIT SIZES. 2.PROVIDE THE FAULT CURRENT AT THE SERVICE. 3. THE LOAD CALCULATIONS USED FOR LIGHTS AND RECEPTACLES ARE GREATLY EXAGERATED PL CORRECT. RAY T MAJUTA DSD CITY OF TUCSON ELECTRICAL PLN CK 11/07/08 |
| 11/12/2008 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/12/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/12/2008 | DROBEY1 | WATER | REVIEW | Needs Review | |
| 11/12/2008 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/12/2008 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/12/2008 | DELMA ROBEY | OUT TO CUSTOMER | Completed |