Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM03529
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2009 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T08CM03529 2/09/09 2308 E. MABEL ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, IECC AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FLOOR PLANS: 1. PROVIDE PLAN FOR THE NEW KITCHEN LAYOUT. ELECTRICAL, PLUMBING, MECHANICAL …? WILL THESE BE A DEFERRED SUBMITAL BY OTHERS? 2. THE WINDOW EAST OF THE FRONT DOOR APPEARS TO BE LESS THAN 2 FEET FROM THE DOOR. PLEASE PROVIDE SAFETY GLAZING. R308 AND R308.4 ITEM 6 FLOOR PLAN: 1. PROVIDE ATTIC ACCESS. R807 STRUCTURAL PLANS: 1. PROVIDE POST/BEAM/FOOTING FOR THE SUPPORT OF THE SOUTH END OF THE RAFTERS OVER THE BREEZEWAY BETWEEN THE WORKSHOP AND THE PORCH. IF SUPPORTED BY THE CANTILEVERED 2-2X8, PROVIDE 2X8/PLATE CONNECTION AND JUSTIFY THE 2-2X8 CANTILEVER. 2. PROVIDE THE TRUSS DATA SHEETS SEALED BY AN ENGINEER REGISTERED IN THE STATE OF ARIZONA. 3. PROVIDE ROOF VENTILATION. R806 SECTIONS - DETAILS - MISC. NOTES: 1. C/A2 ; IS THE R=1 INSULATION IN THE 2X4 WALL A TYPO? IF NOT, PLEASE JUSTIFY. N1102 MECHANICAL PLANS: 1. PLEASE ILLUSTRATE THE COMBUSTION AIR TO THE LAUNDRY ROOM. ELECTRICAL PLANS: 1. RECEPTACLES APPEAR TO BE OVER SPACED. E3801.2.1 2. GENERAL ELECTRIC NOTE 4 / E1 ; PLEASE CHANGE THE 2000 IRC TO THE 2006 IRC. 3. PLEASE ADD A NOTE TO HELP LOCATE THE CLOSET LIGHT. E3903.11 4. PLEASE ADDRESS THE OUTDOOR LIGHTING CODE. PROVIDE CUT SHEETS. 5. PROVIDE A RECEPTACLE FOR FRONT YARD USE IN ACCORD WITH E3801.7 . IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/10/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 02/10/2009 | SUE REEVES | REJECT SHELF | Completed |