Permit Number: T08CM03519
Parcel: 11711096D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03519
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/24/2008 ROBERT SHERRY WATER REVIEW Approved
11/24/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps may require reduced pressure principle backflow preventers. Specify the type of backflow prevention device required for each water connection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson.
2. Provide a design for the support of the hydromechanical grease interceptor along with structural calculations to show that the hydromechanical grease interceptor is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
3. Show how access is provided for maintenance of the hydromechanical grease interceptor. Reference: Section 103.2.3, UPC 2006.
4. Show how the use of an air admittance valve as a cleanout (detail 203/PD-1) complies with Sections 707.1, 707.2, and 707.3, UPC 2006.
5. Provide information to show that the proposed hydromechanical grease interceptor includes an integral flow control device. If not, install a vented, external flow control device per the manufacturer's instructions for each connected fixture, in a readily accessible location. Reference: Section 1014.2.1, UPC 2006.
6. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. the outlet of the grease interceptor is 3", not 2"). Reference: Section 316.4.1, UPC 2006
7. Provide a vent to protect the hydromechanical grease interceptor from siphonage and back-pressure. Reference: Sections 1002.1 and 1014.2.3, UPC 2006.
11/24/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied If the building energy compliance is not in accordance with ASHRAE 90.1, the duct insulation shall be determined by Section 503.2.7, IECC 2006, as amended by the City of Tucson (i.e. the minimum insulation for ducts located in indirectly conditioned spaces within the building envelope is R-4.2). Reference: Section 501.2, IECC 2006, as amended by the City of Tucson.
12/01/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2008 VFLORES1 OUT TO CUSTOMER Completed
12/03/2008 SUE REEVES REJECT SHELF Completed