Permit Number: T08CM03519
Parcel: 11711096D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03519
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Needs Review
11/03/2008 ROBERT SHERRY WATER REVIEW Approved
11/03/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
11/03/2008 DAVE MANN FIRE REVIEW Approved
11/03/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied This project has been denied for the following;
1.Provide a ground size for the 150 kva transformer.
2.The primary feed for the 150 kva transformer shows 3--3/0's and 1 1/0 grd.Should this be 3--3/0's plus a # 6 grd?
3.The secondary feed on the 150 kva transformer shows 3--3/0's and 1--1/0 grd in a 6" conduit. Should this be 4---3/0's and 1 #6 grd.
4.Provide the fault current at the 200 amp fused disconnect at the SES.

Ray T Majuta
DSD City of Tucson
Elect Plan C11/03/08
11/03/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
11/10/2008 CAGUILA1 WWM REVIEW Needs Review
11/10/2008 CAGUILA1 ZONING HC SITE REVIEW Needs Review
11/10/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review