Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03519
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/03/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/03/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/03/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | This project has been denied for the following; 1.Provide a ground size for the 150 kva transformer. 2.The primary feed for the 150 kva transformer shows 3--3/0's and 1 1/0 grd.Should this be 3--3/0's plus a # 6 grd? 3.The secondary feed on the 150 kva transformer shows 3--3/0's and 1--1/0 grd in a 6" conduit. Should this be 4---3/0's and 1 #6 grd. 4.Provide the fault current at the 200 amp fused disconnect at the SES. Ray T Majuta DSD City of Tucson Elect Plan C11/03/08 |
| 11/10/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/10/2008 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 11/10/2008 | CAGUILA1 | ZONING HC SITE | REVIEW | Needs Review |