Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08CM03513
Parcel: 13110034A

Address:
5510 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03513
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2008 STEVE SHIELDS ZONING REVIEW Approved
10/30/2008 JASON GREEN ENGINEERING REVIEW Approved
11/10/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
11/10/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/10/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
11/12/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/12/2008 MARTIN BROWN FIRE REVIEW Approved
11/12/2008 ROBERT SHERRY WATER REVIEW Approved
11/12/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide information to show how the outlet temperature of the hot water is to be limited to 110 degrees at the lavatory. The proposed tankless water heater does not provide for definite temperature settings or prevent modification of the delivery temperature. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
2. Specify the minimum residual water pressure for the water supply calculations. Reference: Section 608.1, UPC 2006.
3. Resize the drainage piping to conform to Table 7-5, UPC 2003, with no more than 3 6-unit traps on a 3" horizontal waste line. Reference: Section 703.2, UPC 2006.
4. Provide cleanouts sized per Section 707.11, UPC 2006.
5. Provide vent piping of sufficient size to comply with Section 904.1, UPC 2006.
11/13/2008 GERRY KOZIOL WWM REVIEW Approved
11/13/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review