Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03492
Parcel: 14043011A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03492
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2008 MICHAEL ST. PAUL ZONING REVIEW Passed
10/28/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006.
10/28/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:1840 E Valencia RD
T08CM03492

1.Provide a diagram for the se3rvice Cabinets on plan, show grounding detail of how service is to be grounded, along with size of conductors to be used.
2.Does this type of service cabinet have an approval for use as service equipment asw per The NEC 2005 Section 230-66?


RT Majuta
DSD Elect Pln Ck
City of Tucson
10/28/08
10/28/2008 ROBERT SHERRY WATER REVIEW Approved
10/28/2008 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved 1) TO USE THE IPC INSTEAD OF UPC REQUIRES AN APPEAL. PLEASE FILE REQUEST OR ALTER CODE ANALYSIS.

2)
10/28/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
10/28/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/28/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
10/28/2008 DAVE MANN FIRE REVIEW Approved
10/28/2008 LHANLY1 ADA REVIEW Passed
10/28/2008 LEERAY HANLY ZONING HC SITE REVIEW Passed
11/07/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Denied