Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03492
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/28/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
10/28/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2006. |
10/28/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:1840 E Valencia RD T08CM03492 1.Provide a diagram for the se3rvice Cabinets on plan, show grounding detail of how service is to be grounded, along with size of conductors to be used. 2.Does this type of service cabinet have an approval for use as service equipment asw per The NEC 2005 Section 230-66? RT Majuta DSD Elect Pln Ck City of Tucson 10/28/08 |
10/28/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/28/2008 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | 1) TO USE THE IPC INSTEAD OF UPC REQUIRES AN APPEAL. PLEASE FILE REQUEST OR ALTER CODE ANALYSIS. 2) |
10/28/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
10/28/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
10/28/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
10/28/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
10/28/2008 | LHANLY1 | ADA | REVIEW | Passed | |
10/28/2008 | LEERAY HANLY | ZONING HC SITE | REVIEW | Passed | |
11/07/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Denied |