Permit Number: T08CM03485
Parcel: 12515122A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM03485
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2008 GERRY KOZIOL WWM REVIEW Approved
11/24/2008 HENRY DURAZO BUILDING-RESIDENTIAL REVIEW Denied 1. Exterior stairs, when restored, shall comply with current code, submitt detailed section and connection at top and bottom. 2. 1/2" cement board required at shower,behind finished material. 3. All windows in habital rooms shall have a u-value of .75 minimum. 4. Specify heights of existing in proposed quest bed room. 5. Complete detailed connection for framing at entry, front and rear at garden room. 6. Bolt sizes and spacing at 3x plate at Mickey Block. 7. Show detail of scoring in Mickey Block to accomadate electical. 8. Information on BTU demand for water heater 8. Wire sizes to all circuits. 9. Smoke alarm location.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
11/25/2008 SUE REEVES REJECT SHELF Completed