Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03466
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/10/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; provide information to show that the air gap complies with the requirement of Section 603.2.1, UPC 2006. The water supply to the evaporative condenser (sheet R8.1) shall be protected with a reduced pressure backflow prevention assembly or an air gap that complies with the requirements of Section 603.2.1, UPC 2006 (see also footnote 2, Table 6-3). 2. Comment not resolved; a check valve is not an approved backflow prevention device. The "emergency discrete spray line" shown in detail 2/R8.1 appears to require backflow protection. Note that the reference to Section 1002 (b) of the 1991 UPC does not appear to be applicable to this situation. Reference: Section 603.0, UPC 2006. |
02/11/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Coordinate the mechanical, electrical, and plumbing drawings; e.g. AC-2 is shown as "not used" on the mechanical drawings but has gas service and a condensate drain provided on the plumbing drawings and electrical power on the electrical drawings. Similarly, EF-11, EF-12 and MAU-6 do not appear to have power. (Note that EF-12 is scheduled as serving a restroom on sheet AC-1.) 2. Comment not addressed. Comment not addressed. Show the size, routing, and termination of the condensate drains the four fan coil units. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006. 3. Comment not addressed. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the evaporative condensing unit. Reference: Section 302.1, IMC 2006. 4. Comment not addressed (Sheet R8.0). Clarify the location of the remote controls for the machinery room - are they at the top of the access ladder or at the base of the access ladder? Reference: Sections 106.3.1 and 1106.5, IMC 2006. 5. AC-6 is supplying more than 2,000 CFM to multiple rooms; it requires a duct smoke detector located in the return duct. Reference: Section 606, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/19/2009 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
02/19/2009 | SUE REEVES | REJECT SHELF | Completed |