Permit Number: T08CM03466
Parcel: 11901076A

Address:
3372 S 6TH AV

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03466
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2008 DAVE MANN FIRE REVIEW Approved
10/28/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; West District; 42,217 Square Feet Retail; $172,210.93

If a demolition will/has occured on property within the past 10 years, impact fee credits may be available for this project.
10/30/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. 1/8" LETTERING IS REQUIRED ON ALL DRAWINGS UNLESS A WRITTEN APPEAL IS APPROVED BY THE BUILDING OFFICIAL, JESSIE SANDERS. THIS APPROVED APPEAL MUST ACCOMPANY DRAWINGS SUBMITTED FOR PLAN REVIEW.
2. GENERAL: REMOVE OR REVISE PLANS/SECTIONS/NOTES FROM THIS TI SET THAT INDICATE THE SHELL WALLS/JOISTS/FRAMING/FOUNDATIONS AS 'NEW' CONSTRUCTION. ALL EXTERIOR WALL SECTIONS (SHEETS A7.0 THROUGH A7.4, ETC.) SHOULD BE REMOVED OR REVISED. ALL REFERENCES TO STRUCTURAL SHOULD BE REMOVED.
3. SHEET A1.1; DETAILS 9/12: REVISE LOCATION OF BOTTOM OF PARKING SIGN TO 7'-0" (84") ABOVE CONCRETE WALK.
4. SHEET A1.1; DETAIL 29: SECTION REFERENCES STRUCTURAL FOR FOUNDATION SYSTEM. SEE NOTE 2.
5. SHEET A1.2; BUILDING DATA: LIST REQUIRED QUANTITY OF PLUMBING SYSTEMS FIXTURES ON DRAWINGS PER IBC TABLE 2902.1.
6. SHEET A2.3; ROOF PLAN: IS THERE ANY WORK ON THIS PLAN THAT IS SPECIFIC TO THE TI ONLY?
7. SHEETS A3.0 THROUGH A5.4: REMOVE THE SHEETS THAT HAVE NOTHING TO DO WITH THE TI.
8. SHEET A6.0; RESTROOM PLANS: PROVIDE DIMENSIONED ELEVATIONS IN ACCESSIBLE RESTROOMS PER ICC/ANSI A117.1-2003, FIGURES 604.4/604.5.1/604.5.2/604.5.3/604.7.
9. SHEET A6.0; RESTROOM ACCESSORIES TABLE: ADD VERTICAL GRAB BAR IN ACCESSIBLE RESTROOMS.
10/31/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T08CM03466
Tenant Improvement Plan (1st Review)

TRANSMITTAL DATE: October 31, 2008

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning cannot approve the tenant improvement plans until the shell building plan and the revised development plan have been approved.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped shell building plan and the revised development plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t08cm03466.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
11/10/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide refrigeration plans sealed by an Arizona Registrant that demonstrate that the design of the refrigeration system for the store complies with the requirements of Chapter 11, IMC 2006. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
3. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
4. This project is under the jurisdiction of the City of Tucson; the 2006 International Mechanical Code with Local Amendments is the relevant code for this project.
5. This is not a complete review; further review will be conducted once sealed plans are submitted.
11/10/2008 ROBERT SHERRY WATER REVIEW Denied The water calculations indicate a demand based on a flush tank system rather than the flush valve system that has been submitted. The greater demand will exceed the maximum 50 GPM limit for 1-1/2" water meter set by Tucson Water.
11/12/2008 LOREN MAKUS ENGINEERING REVIEW Denied The revised development plan must be approved before this plan can be approved.
11/12/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide material standards for all plumbing fixtures being provided by others. Reference: Section 401.1, UPC 2006.
2. Accessible metering faucets shall remain open for a minimum of 10 seconds. Reference: Section 402.1, UPC 2006, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-2003.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. Three of the specified fixtures, the Madera water closet, the Washbrook urinal, and the Oasis PF8AM drinking fountain require a minimum water pressure which is greater than the 15-PSI used in the water pipe sizing calculations (25 PSI for the water closet and 20 PSI for the urinal and the drinking fountain). Revise calculations as necessary. Reference: Section 608.1, UPC 2006.
5. Clarify the size of the medium pressure gas pipe between the corn oven branch and the branch for the corn tanks. Reference: Section 103.2.3, UPC 2006 and Section 402.3, IFGC 2006.
6. Resize the low pressure gas piping serving AC-7per Table 402.4(2), IFGC for the specified gas demand and developed length or provide calculations justifying the submitted pipe size. Reference: Section 402.3, IFGC 2006.
7. Provide a copy of the approved, underground plumbing plans (T08CM02990) for comparison with the proposed tenant improvement plumbing plans. Reference: Section 103.2.3, UPC 2006.
8. Provide upper terminal cleanouts for the two branch drains serving the restrooms. Reference: Section 707.4, UPC 2006.
11/19/2008 GERRY KOZIOL WWM REVIEW Denied PLUMBING TI PLANS DO NOT MATCH SHELL PLUMBING PLANS. NEED TO MODIFY SHELL PLUMBING DRAWINGS PRIOR TO CONSTRUCTION IF INCORRECT. NEED TO RESUBMIT SHELL REVISIONS PRIOR TO TI APPROVAL
11/21/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/24/2008 CINDY AGUILAR OUT TO CUSTOMER Completed