Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03449
Parcel: 10818716A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03449
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
10/22/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations and structural details for the installation of the new roof top unit.
2. Clarify the amount of outside air to be provided by the new roof top unit. Show the common ventilation calculations.
10/22/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1. The new ehaust fan has not been put in the panel.
2. the new new HP-2 has not been put into the pnl.
3. Service receptacle for new HP-2.

Rat T Majuta
DSD C of T
10/22/08
10/22/2008 ROBERT SHERRY WATER REVIEW Approved
10/22/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/22/2008 GERRY KOZIOL WWM REVIEW Approved
10/22/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the plumbing plan with the wste & vent riser diagram.
2. Provide a detail for the installation of the new water heater, showing the shut off valve, heat traps, insulation, T&P relief valve, and the expansion tank.
3. Provide a listing for the new hair washing sinks.
4. Provide water hammer arrestors for the new clothes washer.
10/22/2008 JASON GREEN ENGINEERING REVIEW Approved
10/22/2008 MARTIN BROWN FIRE REVIEW Approved
10/22/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
10/22/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
10/28/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review