Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03449
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
10/22/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations and structural details for the installation of the new roof top unit. 2. Clarify the amount of outside air to be provided by the new roof top unit. Show the common ventilation calculations. |
10/22/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1. The new ehaust fan has not been put in the panel. 2. the new new HP-2 has not been put into the pnl. 3. Service receptacle for new HP-2. Rat T Majuta DSD C of T 10/22/08 |
10/22/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/22/2008 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/22/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
10/22/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plumbing plan with the wste & vent riser diagram. 2. Provide a detail for the installation of the new water heater, showing the shut off valve, heat traps, insulation, T&P relief valve, and the expansion tank. 3. Provide a listing for the new hair washing sinks. 4. Provide water hammer arrestors for the new clothes washer. |
10/22/2008 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
10/22/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
10/22/2008 | RBROWN1 | ADA | REVIEW | Passed | NOT A COT PROJECT |
10/22/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
10/28/2008 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |