Permit Number: T08CM03429
Parcel: 13316031C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03429
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2008 MARTIN BROWN FIRE REVIEW Approved
10/21/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font to a minimum of 1/8", all upper case.
2. Provide balancing information for the air conditioning system.
3. Add a note to ensure that any materials exposed in the return air plenum conform to Section 602.2.1, IMC 2006.
10/21/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/21/2008 ROBERT SHERRY WATER REVIEW Approved
10/21/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/21/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/21/2008 RBROWN1 ADA REVIEW Passed
10/21/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
10/24/2008 CPIERCE1 WWM REVIEW Needs Review
10/24/2008 CPIERCE1 ZONING REVIEW Needs Review
10/24/2008 CPIERCE1 ENGINEERING REVIEW Needs Review
10/24/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review