Permit Number: T08CM03403
Parcel: 105110660

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03403
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/18/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a design along with structural calculations to show how the water heater bracket is attached to the building wall.
2. Clarify the location of the backflow preventer for the Mymyst appliance. If it is located more than 5'-0" above the finished floor, provide a design for a maintenance platform.
3. Provide calculations to show that 55 PSI will be available at the Mymyst appliance (not the site). A 1/2" supply to the unit will have a velocity greater than 8 FPS at 8 GPM.
11/18/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2008 ROBERT SHERRY WATER REVIEW Denied The revised shell drawings indicate that a 1" water meter has been installed to serve the building instead of the 2" meter that had been originally specified. A 1" meter is limited to a demand of 25 GPM by Tucson Water. Provide information to show that the total demand for the building will be less than 25 GPM.