Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03403
Parcel: 105110660

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03403
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2008 GERRY KOZIOL WWM REVIEW Approved
10/20/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 1,903 Square Feet; $6,025.42
11/04/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide plans sealed by an Arizona Registrant, i.e. sign and date all of the submitted sheets. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
3. Comment not addressed. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
4. Comment not addressed. Provide a complete plumbing plan, including the water and waste and vent isometrics. Reference: Section 103.2.3, UPC 2006.
5. Comment not addressed. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
6. Comment not addressed. Show that the location of the backflow preventer conforms to the access and clearance requirements of Section 603.3.4, UPC 2006.
7. Comment not addressed. Show how the new water and waste piping relates to the existing systems. Reference: Section 101.5.1, UPC 2006.
8. Comment not addressed. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
9. Comment not addressed. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves. Reference: Section 609.10, UPC 2006.
10. Comment not addressed. Provide a vent for each fixture trap (e.g. the floor drains). Reference: Sections 901.0 and 910.1, UPC 2006.
11. Confirm that the installation of the plumbing supplies and drains for the Mystic "Mymyst" comply with the listing requirements of the manufacturer, e.g. 55 PSI available water pressure at 8 GPM, location of the water and drain connections.
12. Double check valve assemblies are approved for use with low hazard (pollution) back siphonage and back-pressure situations. Does the material used with the Mystic Mymyst constitute a pollutant or a contaminant (high hazard)? Reference: Sections 205.0 and 218.0, and Table 6-2, UPC 2006.
11/04/2008 ROBERT SHERRY WATER REVIEW Denied Comment not addressed. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions with regard to the location and size of the existing water meter and backflow preventer. Reference: Sections 106.1 and 106.3, IBC 2006, and COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf
11/04/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide plans sealed by an Arizona Registrant, i.e. sign and date all of the submitted sheets. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Comment not addressed. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
3. Comment not addressed. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006
4. Comment not addressed. Show the size, routing, and termination of the condensate drains. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable or absorbing the condensate flow without surface drainage. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006, as amended by the City of Tucson.
5. Comment not addressed. Provide calculations demonstrating adequate ventilation. Note that ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference: Sections 401.2 and 403.3, IMC 2006.
6. Comment not addressed. Clarify if the massage room falls under the requirements of the City of Tucson ordinance relating to massage establishments.
11/05/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 4280 N Oracle 160
T08CM03403


Project denied for following;

1. Electrical Engineer to sign under his stamp and date.
2.Provide existing and new load (this TI ) for current total amperage load on whole service.


Ray T Majuta
DSD City of Tucson
Elect Plan Ck
11-06-08
520-837-4988

Final Status

Task End Date Reviewer's Name Type of Review Description
11/18/2008 CPIERCE1 OUT TO CUSTOMER Completed
11/18/2008 SUE REEVES REJECT SHELF Completed