Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T08CM03354
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2009 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T08CM03354 1/21/09 5832 E. MABEL ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, IECC AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ¼ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SECTIONS - DETAILS - MISC. NOTES: 1. WALL / 6 ; DESCRIBE THE COMPONENTS OF THE NEW WALL VIA A CROSS SECTION. PLATE, BOLTS/PINS, STUDS, SHEATHING. 2. RAFTER / BEAM / 7 ; DESCRIBE / ILLUSTRATE THE RAFTER TO BEAM CONNECTION. 3. GARAGE / 8 ; PLEASE CHECK THE STRENGTH OF THE CONCRETE. ……25,000psi OR DID YOU MEAN 2500psi ? 4. GARAGE / 8 ; WILL THE FLOOR BE REINFORCED WITH WELDED WIRE FABRIC, MESH? IF SO, IT IS COMMONLY DESCRIBED BY IT'S SPACING IN EACH DIRECTION AND GAGE IN EACH DIRECTION. . PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. DRAINS, VENTS, SEWER, WATER DISTRIBUTION UNDER THE FLOOR. 2. PLEASE ILLUSTRATE / NOTE THE ROUTE OF THE P&T LINE FROM THE WATER HEATER. P2803.6.1 3. PLEASE NOTE THE BACKING BOARD FOR TILE SHALL BE CEMENT, FIBER-CEMENT, OR GLASS MAT GYPSUM FOR TILE IN THE TUB AND SHOWER AREAS. R702.4.2 PLEASE NOTE ON FLOOR PLAN 4. DWELLING PLUMBING / 10 , GARAGE PLUMBING / 11 ; PLEASE NOTE A BLUE 18 GA. TRACER WIRE SECURELY ATTACHED TO THE NON-METALIC WATER SERVICE LINE. THE TRACER WIRE FOR PRIVATE SEWERS IS GREEN. 5. GARAGE PLUMBING / 11 ; WHAT IS THE LINE TO THE RIGHT AND PARALLEL TO THE 1" CW LINE TO THE DWELLING? 6. GAS / 17 ; THE 1" GAS LINE BETWEEN THE FURNACE AND THE RANGE APPEARS TO BE INADEQUATE. 7. GAS / 17 ; THE ¾" GAS LINE BETWEEN THE RANGE AND THE SHOP'S WATER HEATER APPEARS TO BE INADEQUATE. MECHANICAL PLANS: 1. DUCTS / 19, 20 ; PLEASE SIZE THE DUCTS. ELECTRICAL PLANS: 1. PANEL SCHEDULES / 13 ; PLEASE PROVIDE CIRCUITS FOR THE SUB-PANELS. CIRCUIT B5, 100 AMPS, ISN'T APPROPRIATE FOR PANEL C, 50AMPS. ARE YOU USING THE BUS COLUMN FOR THE SUB-PANEL DESIGNATION? 2. PROVIDE A RECEPTACLE, 20 A., NORTH OF THE RANGE IF THATIS A TOP. IS IT A TOP OR A BROOM-TYPE CABINET? E3801.4 3. THE RECEPTACLE BY THE LAVATORY IS REQUIRED TO BE ON A 20 AMP CIRCUIT DEDICATED TO THAT RECEPTACLE OR TO THAT BATHROOM. E3803.4 4. PLEASE ADD A NOTE INDICATING THE BEDROOM OUTLETS WILL BE COMBINATION-TYPE ARC-FAULT PROTECTED. E3802.12 5. PLEASE PROVIDE SMOKE DETECTORS IN THE IMMEDIATE AREAS OUTSIDE EACH BEDROOM. R313.2 6. PROVIDE A RECEPTACLE TO SERVE THE FRONT AND THE BACK YARDS. E3801.7 7. PROVIDE A RECEPTACLE WITHIN 6' EAST OF THE OF THE FRONT DOOR IN THE LIVING ROOM. E3801.2.1 8. PROVIDE A RECEPTACLE IN THE MASTER BEDROOM NORTH OF THE BATH DOOR. E3801.2.1 9. PLEASE PROVIDE A NOTE ADDRESSING THE LOCATION OF THE CLOSET LIGHT. E3903.11 10. PROVIDE A WALL SWITCHED LIGHTING OUTLET ON THE EXTERIOR SIDE OF THE SOUTH DOOR OF THE SHOP. E3803.3 11. PLEASE USE THE SUB-PANEL NAME FROM THE ELECTRICAL RISER DIAGRAM ON PAGE 13 AS THE NAME USED TO IDENTIFY THE SUB-PANELS ON THE PANEL SCHEDULE. ONE SUB-PANEL IS IDENTIFIED AS "BATHROOM SUB PANEL" AND THEY AREN'T PERMITTED IN BATHROOMS. 12. PROVIDE LOAD CALCULATIONS TO JUSTIFY THE AMPICITY OF SUB-PANEL B AND CALCULATIONS FOR THE MAIN PANEL. 13. PROVIDE CIRCUIT NUMBERS FOR PANEL C. 14. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED OUTLET BOXES SHALL BE USED, PER E4001.6. 15. THE CIRCUIT SERVING THE RECEPTACLE BY THE LAVATORY ISN'T PERMITTED TO SERVE DEVICES IN OTHER ROOMS. E3603.4 16. PROVIDE A 20 AMP DEDICATED CIRCUIT TO SERVE THE LAUNDRY WITH NO OTHER DEVICES IN OTHER ROOMS. E3603.3 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
| 12/26/2008 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED 5TH FLOOR CREDIT REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/29/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |