Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03328
Parcel: 133380930

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03328
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2009 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS T08CM03328 Rev 2-25-09

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2006 IRC with amendments on 6/12/2007, the 2006 UPC with amendments on 7/10/2007 and effective 1/1/2007 the Inclusive Home Design. All plans should reference these codes. Adopted amendments are found at: http://www.tucsonaz.gov/dsd/Codes___Ordinances/Building_Codes/building_codes.html

GENERAL NOTES:

1. Provide the engineer seal and masonry lintel Detail X on the plans as noted above.

STRUCTURAL PLANS:

1. Provide a minimum opening of 22" by 30" for access and ventilation between existing and new attic areas on the Roof Framing Plan, R807. This opening between attic areas is required for any attic height; needed for air circulation.
2. Clarify the corner window design. The plans show a 3" steel post with double steel lintel, but the attached engineering calculations show an unsupported reinforced masonry lintel, R106.1.1.

SECTIONS - DETAILS:

1. Provide a detail of the corner window design on the plans, R106.1.1.
2. Clarify the intended footer type, R106.1.1. Remove the spread footer detail from the attached engineered calculation.

ELECTRICAL PLANS:

1. Clarify the electrical riser diagram referencing the 2006 rather than the 2003 IRC (two places).
2. Clarify the electrical riser diagram referencing 2 #14 branch circuits to the new addition. Also note circuit 'C' 1 #12.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/03/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
03/03/2009 SUE REEVES REJECT SHELF Completed