Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08CM03326
Parcel: 13727635B

Review Status: Completed

Review Details: SITE

Permit Number - T08CM03326
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2008 DAVE MANN FIRE REVIEW Approved
10/10/2008 SREEVES1 ADA REVIEW Passed
10/13/2008 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Grijalva School Park
T08CM03326
Site Plan (1st Review)

TRANSMITTAL DATE: October 13, 2008

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance.

2. D.S. 2-02.2.1.A.5 Clearly show all property lines on the plan along with lot dimensions and bearings.

3. D.S. 2-02.2.1.A.7 Provide the heights of all proposed ramada and shade structures on the plan. Also provide setback dimensions from all proposed ramada and shade structures to applicable property lines so that the required setbacks can be verified.

4. D.S. 2-02.2.1.A.9 On the bicycle parking detail, 3/HS2.02 include; materials for lighting, paving, and security; fully dimensioned layout; location; specific type of rack and the number of bicycles it supports. The provided detail can only support two (2) bicycles. Zoning was only able to find one (1) location similar to the detail on the site plan. Based on the bicycle parking calculation there are five (5) provided, please clarify.

5. D.S. 2-02.2.2.A.3 Provide a lot coverage calculation for the area of the proposed park.

6. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t08cm03326

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents.
10/13/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 13 OCTOBER 2008
T08CM03326/GRIJALVA SCHOOL PARK - CITY OF TUCSON, PARKS AND
RECREATION DEPARTMENT
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
ADAAG 1994 EDITION

DENIED: SEE COMMENTS BELOW

SHEET SP0.00
1. ACCESSIBILITY FOR THIS PROJECT IS GOVERNED BY ADAAG 1994 EDITION AND 2006 IBC, SECTION 11. PLEASE NOTE IN CODE REVIEW CHECK LIST SCHEDULE
SHEET SP1.01
2. ADD ACCESSIBILITY ROUTE AND VIEWING AREA OF ADDITIVE ALTERNATE #2, SAND VOLLEYBALL COURT. ADD ALSO AT SHEET HS1.02.
3. ADD ACCESSIBLE ROUTE CONNECTION TO EXISTING BUILDING OF ADDITIVE ALTERNATE #3, MULTI-PURPOSE FIELDS. ADD ALSO AT SHEET HS1.03.
4. ADD ACCESSIBLE ROUTE CONNECTION TO EXISTING BASKETBALL BALL COURTS FROM ACCESSIBLE ROUTE OF ADDITIVE ALTERNATE #3, MULTI-PURPOSE FIELDS. ADD ALSO AT SHEET HS1.03.
SHEET HS1.01
5. REFERENCE ACCESSIBLE PARKING SPACES TO DETAIL 8/CG1.02. SEE CHANGE COMMENTS.
6. AS PER 2006 IBC, SECTION 1106.7.1 AND ADAAG, SECTION 4.6.6, AN ACCESSIBLE PASSENGER LOADING ZONE.
SHEET CG1.01
7. PROVIDE ADDITIONAL CLARIFICATION FOR DIFFERENT TYPES OF SPOT ELEVATION INDICATORS; G, TC, IF NO I.D. MARK WHAT DOES IT MEAN, ETC.
SHEET CG1.02
8. PROVIDE AN ACCESSIBLE SIGN ELEVATION DETAIL.
9. AT DETAIL "B":
A. RELOCATE ACCESSIBLE SIGN TO JUST BEHIND THE CURB LINE ON THE SIDEWALK SIDE AND REFERENCE TO NEW SIGN DETAIL AS PER COMMENT 8 ABOVE.
B. SHOW ACCESSIBILITY ACCESS FROM THE PARKING AISLE TO THE ACCESSIBLE ROUTE WITH RAMPS AS PER SECTION 4.7 OR 4.8.
C. ACCESSIBLE ROUTE TO BE A MINIMUM OF 4' WIDE.
SHEET CG1.03
10. DITTO NOTES 5 AND 6 ABOVE.
11. NOTE 8 REFERS TO COT STD DTL 213. THIS IS FOR WEDGE CURBS. WEDGE CURBS ARE NOT SHOWN ON ANY OF THE SITE PLANS.
SHEETS CG1.04 AND CG1.05
A. DITTO NOTES 2, 3 AND 4 ABOVE.
B. SHOW SPOT GRADES ALONG THE NEW ACCESSIBLE ROUTE SUFFICIENTLY TO SHOW COMPLIANCE WITH SECTION 4.3.7.
SHEETS CG1.06
12. DITTO NOTES 5 AND 6 ABOVE.
13. SEE NEW ACCESSIBLE PARKING SIGN DETAIL ON SHEET CG1.02.
14. IDENTIFY "VAN ACCESSIBLE" SPACE.

END OF REVIEW
10/17/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: October 20, 2008
SUBJECT: Site Plan
TO: Steve Hagedorn
LOCATION: 1795 W Drexel Road, T15S, R13E, Section 10, Ward 1
REVIEWERS: Bianca Ramirez, CFM
ACTIVITY: T08CM03326 (First Review)


RESUBMITTAL REQUIRED: Site Plan, Hydrology and Hydraulic Report

SUMMARY: Engineering Division of Development Services Department has received and reviewed the proposed site plan for the above referenced property. Engineering Division does not recommend approval of the site plan at this time. Please address the following review comments prior to the next submittal.

Please include a response letter to the commends along with the corrected copies of the site plan.

Site Plan:

1. The most recent aerial photo of the building does not match what is depicted on the site plan. Please modify site plan to represent actual parcel property boundaries on site plan.
2. Please label lot dimensions and bearings per D.S. 2-02.2.1.5.
3. Provide all existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use per D.S. 2-02.2.1.6.
4. DS Sec.2-02.2.1.A.10: Provide existing and future site visibility triangles (SVT), labeled and dimensioned. Refer to DS Sec.3-01.5.3 for line of site matrix for SVTs.
5. Label width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11. Dimension driveways and PAALs.
6. DS Sec.2-02.2.1.A.11 & DS Sec.3-01.3.2.C: Label radii for concrete curbs per City of Tucson/Pima County Standard Detail 213 (PC/COT SD 213) at the driveway entrance along S Oak Tree Drive
7. Call out radius on plans for curb islands.
8. Please label all width of vehicular, bicycle, pedestrian, and handicapped circulation clearly identified per D.S. 2-02.2.1.12.
9. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. If not cut and fill is taking place indicate the quantity of zero (0) on the plan. Estimated cut and Fill: Cut = 0 and Fill = 0 will suffice.
10. Please show dimensioned right-of-way for Oak Tree Drive and Drexel Road and lable as public per D.S. 2-02.2.1.19.
12. DS Sec. 2-05.2.4.H.2: Provide the right-of-way (ROW) recordation information for Drexel Road and Oak Tree Drive..
13. Verify that all easement of record have been graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
14. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
15. Show all fences, walls, or vegetation for screening and sight visibility by type, material, height, location and spacing per D.S. 2-02.2.1.27.
16. Show site plan activity number in the lower right hand corner of each sheet.
17. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
18. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
19. Provide location of trash pick up along with maneuverability as well as details for trash enclosure or appropriate documentation from Env. Services.
20. Provide spot elevation for flowline of channel to show adequate flow and convayance in channel. Minimum 1% is needed.
21.. Additional comments may be forthcoming.

Hydrology and Hydraulic Report - Approved

If you have any questions, I can be reached at 837-4928 or Bianca.Ramirez@tucsonaz.gov

Bianca C. Ramirez
Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4928 office
(520) 879-8010 fax
11/03/2008 JOE LINVILLE NPPO REVIEW Approv-Cond
11/03/2008 JOE LINVILLE LANDSCAPE REVIEW Approv-Cond 1) Revise the landscape plans to incorporate any changes requested by other sections. The plans will be stamped approved when revisions are complete.

2) Revise the planting plan along Oak Tree Drive to locate the Hesperaloe parviflora outside of the sight visibility traingles. Occasionally, these plants have been severely pruned or removed altogether to meet SVT requirements at other sites in the City.
11/03/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the site drawings to show the source of the domestic water (i.e. meter and backflow preventer locations and sizes).

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
12/08/2008 SUE REEVES REJECT SHELF Completed