Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03295
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2008 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 10/08/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | Project has been denied for the following reasons; 1. Each meter on the plan if future or not is required to have an address listed on the application.One new service and three new on plan require addresses. 2.Electrical plan is ok. Ray T Majuta DSD City of Tucson Electrical Plan Ck 10/08/08 |
| 10/08/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Passed | |
| 10/08/2008 | ENEWCOM1 | ADA | REVIEW | Passed | |
| 10/14/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a mechanical design that is coordinated with the architectural design. 2. Provide ventilation calculations. 3. Clarify the scope of work to be accomplished, e.g. is any ductwork included in this project, how is the condensate to be handled, etc. |
| 10/14/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/14/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/14/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/14/2008 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures indicated on the plans. |
| 10/27/2008 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 10/27/2008 | CAGUILA1 | FIRE | REVIEW | Needs Review |