Permit Number: T08CM03290
Parcel: 125170380

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03290
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
10/07/2008 JASON GREEN ENGINEERING REVIEW Approved
10/07/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
10/07/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/07/2008 RONALD BROWN ZONING HC SITE REVIEW Passed
10/07/2008 MARTIN BROWN FIRE REVIEW Approved
10/08/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/08/2008 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
10/08/2008 ROBERT SHERRY WATER REVIEW Approved
10/08/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/08/2008 DROBEY1 WWM REVIEW Needs Review
10/08/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vent to protect the trap for the 2-compartments that are directly connected. Reference: Section 1014.1.1, UPC 2006.
2. Provide clarifying details for the construction of the water heater platform ( e.g. connections to the floor and wall) and the operating weight of the water heater. Reference: Section 103.2.3, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2008 DELMA ROBEY APPROVAL SHELF Completed
10/08/2008 DELMA ROBEY OUT TO CUSTOMER Completed
10/08/2008 DELMA ROBEY REJECT SHELF Completed