Permit Number: T08CM03271
Parcel: 11451216G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03271
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2008 TERRY STEVENS ZONING REVIEW Approved
10/06/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Revise the sequence of operation for the restroom exhaust fans to prevent recirculation of the air from the restrooms. Reference: Section 403.2.1, IMC 2006
10/06/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
10/06/2008 ROBERT SHERRY WATER REVIEW Approved
10/06/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
10/06/2008 LOREN MAKUS ENGINEERING REVIEW Approved
10/06/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference: Section 106.1.1, IBC 2006
10/06/2008 MARTIN BROWN FIRE REVIEW Approved
10/06/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
10/10/2008 DROBEY1 WWM REVIEW Needs Review
10/10/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/10/2008 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/10/2008 DELMA ROBEY OUT TO CUSTOMER Completed