Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08CM03250
Parcel: 10601247B

Address:
125 E PRINCE RD

Review Status: Completed

Review Details: SITE

Permit Number - T08CM03250
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2008 DAVE MANN FIRE REVIEW Denied Please clarify location of Central Plant facility in relation to the new building and fire department access.
Please provide details about signage required for mechanical refrigeration systems as outlined by the 2006 IFC, Section 606.
Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
10/10/2008 ANDREW CONNOR NPPO REVIEW Passed
10/10/2008 ANDREW CONNOR LANDSCAPE REVIEW Passed
10/15/2008 RONALD BROWN ZONING HC SITE REVIEW Denied 15 OCTOBER 2008
T08CM03250/PRINCE ELEMENTARY AMPHITHEATER SCHOOL DISTRICT NO 10
REVIEWED BY RON BROWN

ACCESSIBLE REVIEW
2006 IBC/ICC ANSI 117.1

DENIED: SEE COMMENTS BELOW

SHEET SD01
1. PLEASE PROVIDE LARGE SCALE DETAIL OF THE MARKED CROSSING CURB RAMP COMPLYING WITH 2006 IBC, ICC ANSI 117.1, SECTION 406. SHOW ALL DIMENSIONS, SLOPES, DETECTABLE WARNING STRIPS AND ETC.
2. PLEASE SHOW LARGE SCALE DETAIL OF ACCESSIBLE PARKING COMPLYING WITH ICC 117.1 SECTIONS 502 AND 405. SHOW DIMENSIONS OF ALL PARKING SPACES, LOCATE VAN ACCESSIBLE SPACE, SLOPES, SIGNAGE, SHOW SURFACE MOUNTED CURB AT ACCESSIBLE ROUTE FLUSH SITUATIONS WITH ASPHALT (SEE ZONING SEPARATION REQUIREMENT COMMENTS) AND ACCESSIBLE ROUTE.
3. NOTE 11 REFERENCE AT THE ACCESSIBLE PARKING SPACES IS INCORRECT.
4. IF THE PURPOSE OF THE VEHICLE LOOP IS TO PROVIDE A PASSENGER DROP OFF ZONE, THEN AS PER 2006 IBC, SECTION 1106.7.1, ONE ACCESSIBLE LOADING MUST BE PROVIDED. PLEASE CLARIFY
SHEET SD02
5. DETAIL H1:
A. GENERIC PARKING PLANS ARE NOT SUFFICIENT. PLEASE PROVIDE LARGE SCALE DETAIL OF ACTUAL ACCESSIBLE PARKING LAYOUT SHOWN ON SHEET SD01 AND AS PER COMMENT 2 ABOVE.
B. DELETE NOTE 1. PROVIDE BOTTOM OF MAIN SIGN 7' ABOVE FINISHED GRADE.
C. PROVIDE A "VAN ACCESSIBLE SIGN JUST BELOW THE MAIN ACCESSIBLE SIGN. NOTE ON SD01 WHICH SPACE IS TO BE "VAN ACCESSIBLE".
SHEET C03
6. PROVIDE SPOT GRADES ALONG THE ACCESSIBLE TO SUFFICIENTLY SHOW SLOPE COMPLIANCE WITH ICC 117.1, SECTION 403.3.
7. AT NOTE 5a DELETE ALL REFERENCE TO COT 207, THIS IS FOR RIGHT OF WAY DETAILS ONLY. PLEASE CHANGE THE NOTE TO REFERENCE ICC ANSI 117.1, SECTION 406 CURB RAMPS AND DETECTABLE WARNING STRIPS.
8. DELETE THE NOTE 5a REFERENCE AT THE ACCESSIBLE PARKING SPACES AND DIRECT COMPLIANCE REFERENCE TO ICC ANSI 117.1, SECTION 405, SIDE WALK RAMPS.

END OF REVIEW
10/15/2008 RBROWN1 ADA REVIEW Passed NOT A COT PROJECT
10/27/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/26/2008 CINDY AGUILAR OUT TO CUSTOMER Completed
11/26/2008 SUE REEVES REJECT SHELF Completed