Review Details: COMMERCIAL TI
Permit Number - T08CM03244
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2008 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/06/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/06/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/08/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE CALCULATIONS FOR NEW BEAM, COLUMN, AND FOOTING AT DRIVE-THROUGH AREA. THESE ISSUES FROM THE FIRST REVIEW WERE NOT ADDRESSED. |
| 10/09/2008 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 10/17/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the plumbing floor plan and the waste and vent riser diagram. Show each vent on the riser diagram. 2. Show the size of each pipe on the riser diagram. |
| 10/24/2008 | CPIERCE1 | ZONING | REVIEW | Needs Review |