Permit Number: T08CM03244
Parcel: 14029008B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03244
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2008 DAVID RIVERA ZONING REVIEW Needs Review
10/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/01/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/01/2008 ROBERT SHERRY WATER REVIEW Approved
10/01/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE CALCULATIONS FOR NEW BEAM, COLUMN, AND FOOTING AT DRIVE-THROUGH AREA.
10/01/2008 DROBEY1 WWM REVIEW Needs Review
10/01/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vent for each fixture trap. Reference: Sections 901.0 and 910.1, UPC 2006.
2. Modify trap arm lengths to conform to Table 10-1, UPC 2006. Reference: Section 1002.2, UPC 2006.
3. Provide an accessible cleanout in the vertical portion of the foot vent for the island sink. Reference: Section 909.0, UPC 2006
10/01/2008 DROBEY1 ENGINEERING REVIEW Needs Review
10/01/2008 DROBEY1 FIRE REVIEW Needs Review
10/01/2008 ENEWCOM1 ADA REVIEW Passed
10/01/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
10/01/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2008 DELMA ROBEY OUT TO CUSTOMER Completed