Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03242
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:96 E Limberlost T08CM03242 Solar Water Heater These plans have been denied for the following ; 1. There has been no electrical circuitry drawn in to feed the electrical elements of the water heater.provide a disconnect at WH site and circuit size. Provide location of panel feed going to and circuit being used,show load added to panel and availabity of that panel to handel load. 2. A receptacle my be required for the thermostat control box. Ray T Majuta DSD El Plan Ck City of Tucson 10/22/08 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/23/2008 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 10/23/2008 | SUE REEVES | REJECT SHELF | Completed |