Permit Number: T08CM03242
Parcel: 105123350

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM03242
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
10/01/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the sizing calculations for the expansion tank, including the adjustments for the Dowfrost heat tranfer fluid. Provide an expansion tank listed for the proposed operating conditions. Reference: Sections 1009 and 1402.5.4, IMC 2006.
2. Specify the T&P relief to be used. Reference: Section 1402.5.1, IMC 2006.
3. Provide listing information for the solar collector system components.
10/01/2008 JASON GREEN ENGINEERING REVIEW Approved
10/01/2008 ROBERT SHERRY BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2008 GERARDO BONILLA OUT TO CUSTOMER Completed