Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03221
Parcel: 126162840

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM03221
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2009 GERRY KOZIOL WWM REVIEW Approved
03/25/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 3-27-09
Activity: T08CM03221
Address: 4021 E. Calle Chica
Applicant: Earl C. Yousey IV

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.
2. Any architect and/or engineer involved in the design of the structure shall seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

3. Provide construction plans for the detached ramada.

SITE PLAN:
4. Specify the location of all utility lines and service meters, R106.1.1.

PLUMBING PLAN:
5. Specify the diameter of the water supply line and the size of the water meter, UPC Table 6-6.

MECHANICAL PLAN:
6. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review